In this short Q&A podcast episode, Bryan answers Jeremy's question about checking the charge on rooftop units, and he gives some RTU tips.
Rooftop units often come in sets, so you can use a thermal camera to look at all of the RTUs and compare them. A thermal imaging camera may even show you where subcooling begins in the condenser, which can be a useful diagnostic hack. Try to avoid hooking up gauges each time you check the charge on a rooftop; RTUs have a fixed factory charge, and losses from your gauges can add up over time. Your senses will also come in handy; check for odd sights, sounds, and smells.
Checking suction pressure and superheat is less risky and imperfect, but it'll give you some diagnostic data. You can also check discharge temperatures to check for signs of compressor overheating (remember: 225 stay alive).
Here are some tips for RTUs:
Have a question that you want us to answer on the podcast? Submit your questions at https://www.speakpipe.com/hvacschool.
Purchase your virtual tickets for the 5th Annual HVACR Training Symposium at https://hvacrschool.com/Symposium24.
Subscribe to our podcast on your iPhone or Android.
Subscribe to our YouTube channel.
Check out our handy calculators here or on the HVAC School Mobile App for Apple and Android.
Click on a timestamp to play from that location
0:00.0 | Hello, this is the HVAC school podcast. This is a short Q&A podcast. Jeremy asks about |
0:11.2 | rooftop units. Jeremy use speakpipe, so speakpipe.com |
0:15.1 | slash HVAC school. |
0:16.3 | That's how he asked the question. |
0:18.0 | And so we're going to hear from Jeremy right after |
0:20.9 | we hear from our great sponsors. Field Piece. Field Piece.com and specifically |
0:27.0 | the SR 47 Wireless Refrigerant Scale the new heavyweight champion of |
0:31.6 | digital scales. |
0:33.0 | carrier and carrier.com. |
0:36.0 | Santa Fe dehumidifiers in their new five-year complete replacement coverage. |
0:42.0 | Find out more at HVacr School.com slash Santa Fe. |
0:46.3 | Refrigeration Technologies at Refriggedec.com. |
0:52.2 | My question would be on rooftops trying to check charge. I use probes. Where's the best place to put like our temperature clamps? Really anything to do with rooftops, service, maintenance, checking them out. |
1:05.0 | All right, thanks for the question, Jeremy. So you started off by asking about checking a |
1:09.0 | charge on rooftop units, and I always challenge that. I don't challenge it because what you're |
1:15.4 | saying is checking the operation or confirming the operation of the system. |
1:18.9 | So how do you check that? How do you confirm that? One of the first and very nice things about |
1:22.9 | rooftop units is that usually there's more than one. That's not always the case but |
1:26.6 | often there is. You're on a roof and even if there's other tenant spaces over there I |
1:29.8 | mean you're not supposed to touch their stuff but one thing that you can do is use a |
1:34.4 | thermal imaging camera. And obviously thermal imaging cameras you can't use |
1:38.7 | them for the absolute measurement very often. So like saying, hey, that |
... |